2022 QLD SMOKE ALARM LEGISLATION
Why Choose Auscoast Fire Services
14 years of specialisation in the fire industry
Trusted by the biggest names
Peace of mind warranty
Simple Pricing
Pricing
...........simplified
1 Smoke Alarm Supplied and Installed
3 Smoke Alarms Supplied and Installed
5+ Smoke Alarms Supplied and Installed
$315.00 inc.GST
$450.00 inc.GST
$550.00 inc.GST
Overview
APPLICABLE TO:
EXISTING DWELLINGS FOR OWNERS / OCCUPIERS+
DWELLINGS BEING SOLD, LEASED OR AN EXISTING LEASE IS RENEWED++
NEW DWELLINGS AND DWELLINGS BEING SUBSTANTIALLY RENOVATED
Click to view : Clarification of requirement flowchart
Installation Requirements
-
Smoke alarms must be installed on each storey
-
in each bedroom; and
-
in hallways which connect bedrooms and the rest of the dwelling; or
-
if there is no hallway, between the bedrooms and other parts of the storey; and
-
if there are no bedrooms on a storey at least one smoke alarm must be installed in the most likely path of travel to exit the dwelling.
-
Smoke alarms must be either hardwired or powered by a non-removable 10-year battery, or a combination of both may be allowed.
-
Where practicable smoke alarms must be placed on the ceiling. Smoke alarms must not be placed:
-
within 300mm of a corner of a ceiling and a wall;
-
within 300mm of a light fitting;
-
within 400mm of an air-conditioning vent;
-
within 400mm of the blades of a ceiling fan.
-
Product Requirements
Smoke alarms in all dwellings must:
​
-
Be photoelectric (AS 3786-2014)
-
Not contain an ionisation sensor
-
Be less than 10 years old
-
Operate when tested
-
Be interconnected with every other smoke alarm in the dwelling so all activate together on the alarm.